Technische Daten

hygrotest 600

 

Electrical connection

hygrotest 600

The hygrotest 600 has two analog outputs ( 4 to 20 mA each in 4-wire technology)

TerminalTerminal allocation
1Measurement signal humidity (+) and simultaneously supply connection 12 to 30 VDC (+)
2Measurement signal humidity (-) and simultaneously supply connection GND (-)
3Measurement signal temperature (+) and simultaneously supply connection 12 to 30 VDC (+)
4Measurement signal temperature (-) and simultaneously supply connection GND (-)

hygrotest 600 is supplied via the humidity terminal. The temperature output, where applicable, is only functional when the humidity circuit is supplied with current. This also applies in combination with all displays.

Technische Daten

hygrotest 650

 

Electrical connection

hygrotest 650 (2-wire or 4-wire technology)

The hygrotest 650 offers different order options for the analog signals: 4 to 20 mA (2-wire) as well as the 4-wire options 0 to 1 V / 0 to 10 V / 0 to 20 mA (or 4 to 20 mA with hygrotest 650 HP)

Electrical connection with 2-wire technology

TerminalTerminal allocation channel 1
1Measurement signal output channel 1 (+) and simultaneously supply connection 12 to 30 VDC
2Measurement signal output channel 1 (-) and simultaneously supply connection GND (-)
3not used
4not used

sowie

TerminalTerminal allocation channel 2
1Measurement signal output channel 2 (+) and simultaneously supply connection 12 to 30 VDC
2Measurement signal output channel 2 (-) and simultaneously supply connection GND (-)
3not used
4not used
hygrotest 650 with putput 4 to 20 mA (2-wire technology) is supplied via the humidity terminal. The temperature output is only functional when the humidity cicuit is supplid with current.

Electrical connection with 4-wire technology

The output variants 0 to 20 mA, 0 to 1 V, 0 to 10 V are only possible with 4-wire technology (4 to 20 mA only with hygrotest 650 HP). This means that two terminals each (1 and 2) per terminal block are for supply. Two terminals each (3 and 4) per terminal block are signal outputs.
Manual switching of the analog outputs is not permitted. Please order the variant suited to your application.

TerminalTerminal allocation channel 1
1Supply connection 12 to30 VDC (+)
2Supply connection GND (-)
3Measurement signal output channel 1 (+)
4Measurement signal output channel 1 (-)

oder

TerminalTerminal allocation channel 2
1Supply connection 12 to30 VDC (+)
2Supply connection GND (-)
3Measurement signal output channel 2 (+)
4Measurement signal output channel 2 (-)

Earthing the hygrotest 650

Because of the metal housing, earthing the instrument is recommended. This is carried out as follows:

Earthing the hygrotest 650

Unscrew the cover of the hygrotest 650. The hygrotest then looks like this:

As can be seen in the illustration, the PE connection is situated in the bottom right of the housing base. It is an M5 thread. You should therefore use an M5 screw.

The connection should look like this: